Search found 6413 matches

by Robert
Thu Feb 03, 2011 5:59 pm
Forum: Nordyne Service & Repair
Topic: Intertherm FEH-023HA blows cold air
Replies: 1
Views: 2916

Re: Intertherm FEH-023HA blows cold air

Hi,

Most likely a sequencer problem.


Sequencer # 901076 can be seen and ordered from here by paging down to it :

http://www.aberdeenhomerepair.com/store ... er-4-stage



Thanks,
Robert
by Robert
Thu Feb 03, 2011 4:51 pm
Forum: Coleman Service & Repair
Topic: coleman7975-856 wont fire
Replies: 1
Views: 1488

Re: coleman7975-856 wont fire

Hi,

Inspect the burner tube and burner orifice/spud for clogs/blockages (spider-web-bugs).

IF all clear, will need an hvac tech who knows his trade, the last one does/did not qualify.



Thanks,
Robert
by Robert
Wed Feb 02, 2011 4:21 pm
Forum: Coleman Service & Repair
Topic: Coleman 7655-856
Replies: 1
Views: 2210

Re: Coleman 7655-856

Did you check the gas valve for 24vac ? Check the burner tube and burner orifice for clogs (spider-web-bugs).



Thanks,
Robert
by Robert
Tue Feb 01, 2011 6:41 pm
Forum: Coleman Service & Repair
Topic: help
Replies: 1
Views: 1317

Re: help

Hi, Go here for steps to troubleshoot your Blend Air System: http://www.mobilehomerepair.com/hvac/ArticleBlendAir.html You can disconnect it for now and work toward finding the problem and repairing when it is warmer. It is a separate system from your furnace and is not needed in order to operate th...
by Robert
Tue Feb 01, 2011 6:26 pm
Forum: Nordyne Service & Repair
Topic: Nordyne RC92+ Gas furnace
Replies: 5
Views: 4008

Re: Nordyne RC92+ Gas furnace

Hi, I deleted the other extremely long post because I do not have time unfortunately to read all that and do not need the sequences of your furnace operation spelled out for me. It also may have some info that is not allowed on here for the viewing public. Here is a link for my troubleshooting fee i...
by Robert
Tue Feb 01, 2011 5:26 pm
Forum: Nordyne Service & Repair
Topic: Nordyne RC92+ Gas furnace
Replies: 5
Views: 4008

Re: Nordyne RC92+ Gas furnace

Hi,

It may work, but the reason it was not getting voltage could be due to a safety issue interrupting the power to it for safety.


IF that was/is the case, doing what you did bypassed that and could create a dangerous
situation.


Thanks,
Robert
by Robert
Tue Feb 01, 2011 5:23 pm
Forum: Nordyne Service & Repair
Topic: This may sound like a dumb question....
Replies: 1
Views: 2193

Re: This may sound like a dumb question....

Hi, What you described could be the sequencers or the limit switches. Only way to know would be to test them when it is happening. Anytime your furnace is not functioning properly, there is a risk of an electrical mishap causing a fire IF you continue to operate the furnace. I would only replace wha...
by Robert
Tue Feb 01, 2011 5:14 pm
Forum: Nordyne Service & Repair
Topic: Nordyne RC92+ Gas furnace
Replies: 5
Views: 4008

Re: Nordyne RC92+ Gas furnace

What is the furnace model number ? The gas valve not working may be to a safety issue, jumping it could prove dangerous and is not advised.



Thanks,
Robert
by Robert
Tue Feb 01, 2011 4:18 pm
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-015HA only gets warm
Replies: 9
Views: 7808

Re: Nordyne E2EB-015HA only gets warm

Hi Terri, Ok, you've been reading some in the forums it appears. Meter set to read above 240VAC, one meter lead on far right and other lead on far left coil terminals on white ceramic insulators. WITH a call for heat after 30-45 secs., you should read 240VAC across them. IF you do not, send me an em...
by Robert
Tue Feb 01, 2011 4:12 pm
Forum: Coleman Service & Repair
Topic: Evcon EB15B not heating properly
Replies: 5
Views: 2774

Re: Evcon EB15B not heating properly

Hi Barry,


Keep me posted if you need anything else.



Thanks,
Robert
by Robert
Tue Feb 01, 2011 4:11 pm
Forum: Coleman Service & Repair
Topic: DGAT070BDD Heater
Replies: 4
Views: 2552

Re: DGAT070BDD Heater

Hi Rob, That was the next thing I was going to ask IF the flame sensor cleaning did not help. ALL Coleman furnaces that fell under the recall program needed to be inspected and repaired if there was a problem. You could have issues with your heat exchanger. IF they do not find anything wrong or cann...
by Robert
Tue Feb 01, 2011 12:25 am
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-015HA only gets warm
Replies: 9
Views: 7808

Re: Nordyne E2EB-015HA only gets warm

Hi Terri,

You will need to find someone with experience in using it as this is high voltage and too dangerous for a first time DIY attempt at it.


Thanks,
Robert
by Robert
Mon Jan 31, 2011 9:55 pm
Forum: Coleman Service & Repair
Topic: DGAT070BDD Heater
Replies: 4
Views: 2552

Re: DGAT070BDD Heater

Hi Rob,

Pull the remote flame sensor and clean the rod with steel wool. Do not touch it with your hands and be careful not to damage the ceramic shroud.



Thanks,
Robert
by Robert
Mon Jan 31, 2011 9:45 pm
Forum: Coleman Service & Repair
Topic: eb23b
Replies: 1
Views: 1300

Re: eb23b

Hi Jim, For the heating elements to become energized, one of two things must occur. Either there is power getting through on the sequencer side due to a short or stuck sequencer contact. Or, part of the element coil has fallen down and is touching the frame or wall of furnace creating a pathway back...
by Robert
Mon Jan 31, 2011 9:10 pm
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-015HA only gets warm
Replies: 9
Views: 7808

Re: Nordyne E2EB-015HA only gets warm

Hi Terri,

Do you have a volt meter or can you get one and do some tests or have a neighbor/friend that can do some tests ?


Thanks,
Robert