Search found 7 matches

by sandpointspud
Mon Feb 21, 2011 11:52 am
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Re: Blower

Hi Robert,
Yes Please can you send me the number again. What could be taking the sequencer out. It is only about a month old.
by sandpointspud
Sun Feb 20, 2011 4:30 pm
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Re: Blower

Here are the test results from the sequencer.
With call for heat, fan set to auto:
H1/H2 24vac
H3/H4 24 vac
M1/M2 240vac
M2/M3 0vac

Hope this helps
Don
by sandpointspud
Sun Feb 20, 2011 2:56 pm
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Re: Blower

Hi Robert,
Can you let me know how to test sequencer and blower relay now. The T-Stat tested fine. Fan will not run when in auto except for after the call for heat. It seems to run on cool down
by sandpointspud
Mon Feb 14, 2011 3:39 pm
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Re: Blower

Hi Robert, I found a Yellow wire that goes from the transformer to the circuit breaker that was not hooked up. Now the fan will run in the "on" position but not in the "auto" Position. Sequencer is only 1 month old. If fan comes on and runs, that must mean the relay is good too? ...
by sandpointspud
Fri Feb 11, 2011 11:34 pm
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Re: Blower

Thanks, Tested the thermo and it seems to be fine. The blower now operates when it feels like it. Sometimes runs and other times it doesn't. Could it be the fan switch?
by sandpointspud
Wed Feb 09, 2011 9:20 pm
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Re: Blower

Thanks Robert,
Is there a way I can test the thermostat? I will check for loose wires
by sandpointspud
Wed Feb 09, 2011 2:15 pm
Forum: Coleman Service & Repair
Topic: Blower
Replies: 13
Views: 6256

Blower

Hi I have a EB17B and just replaced the sequencer a few weeks ago. At that time the fan would not turn off. Now there are times it wont come on on either auto or the on position of thermostat. After some time being off, it will start to work again. Not sure what part needs replaced.

thanks