Search found 8 matches

by jnoscal
Fri Jul 12, 2013 9:14 am
Forum: Nordyne Service & Repair
Topic: E2EB-020HA Help
Replies: 0
Views: 10194

E2EB-020HA Help

I am having an issue with my AC unit. It is cold, but the blower does not seem to be pushing air well that the house is actually getting warmer. Is this common with this model? My house was built in 2000 and we purchased it in 2006. If this is related to the sequencer, is the sequencer a common prob...
by jnoscal
Fri Dec 10, 2010 11:18 pm
Forum: Nordyne Service & Repair
Topic: E2EB-020HA Fan relay help
Replies: 1
Views: 2029

E2EB-020HA Fan relay help

My fan on my furnace model E2EB-020HA is not shutting off. I traced it back to my relay, but I need to make sure I order the right part number. Please tell me which part to order as soon as you can.

Thanks,
Jayson
by jnoscal
Sun Jan 18, 2009 11:33 am
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-020HA Weak Heat
Replies: 10
Views: 4357

Hi Robert,

The part has been ordered. Hopefully I can get it in hand by Wednesday. I'll post to this again a couple days after the part is installed to let you know whether it is working properly.

Again, thanks for all your help. It is really appreciated.

Jayson
by jnoscal
Fri Jan 16, 2009 6:56 pm
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-020HA Weak Heat
Replies: 10
Views: 4357

Hi Robert,

Yes, the part number would be great. I can order it today and hopefully have it installed by Wednesday.

Thanks again for all your help.

Jayson
by jnoscal
Fri Jan 16, 2009 4:59 pm
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-020HA Weak Heat
Replies: 10
Views: 4357

Hi Robert, I checked the coils with a meter with the unit on. The unit is running a 240VAC line. The bottom element has 230VAC running to each terminal. The top element has nothing to either terminal. There is 230VAC going into the transformer and to each terminal on the right side as well as the l...
by jnoscal
Fri Jan 16, 2009 4:52 pm
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-020HA Weak Heat
Replies: 10
Views: 4357

Hi Robert, I checked the coils with a meter with the unit on. The unit is running a 240VAC line. The bottom element has 230VAC running to each terminal. The top element has nothing to either terminal. There is 230VAC going into the transformer and to each terminal on the right side as well as the li...
by jnoscal
Fri Jan 16, 2009 5:25 am
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-020HA Weak Heat
Replies: 10
Views: 4357

Hi Robert, I was looking some more at it last night and found a pinched gray wire connected to the thermocouple. I cut and re-spliced that in and it has allowed the house to heat up to the set point. Unfortunately, the fan is now continually running and does not shut off until I temporarily drop the...
by jnoscal
Thu Jan 15, 2009 7:49 pm
Forum: Nordyne Service & Repair
Topic: Nordyne E2EB-020HA Weak Heat
Replies: 10
Views: 4357

Nordyne E2EB-020HA Weak Heat

Hi, I came home one day last week and my thermostat was reading 57 degrees. The set point for the heater to kick on is at 65. The blower was running, but only cold air was coming out. I flipped off the breaker and flipped it back on about 10 minutes later and it slowly started to heat the house. I w...