Search found 3 matches
- Mon Nov 14, 2011 3:57 pm
- Forum: Nordyne Service & Repair
- Topic: E2EB-012 Low Voltage
- Replies: 3
- Views: 4119
Re: E2EB-012 Low Voltage
Last update, fixed low voltage problem, there was a loose connection inside the outer unit. Had hvac tech come by this morning to check the compressor problem. Guess what, bad compressor. Goodbye $1175 dollars.
- Sun Nov 13, 2011 5:50 am
- Forum: Nordyne Service & Repair
- Topic: E2EB-012 Low Voltage
- Replies: 3
- Views: 4119
Re: E2EB-012 Low Voltage
Update...was mis-reading the digital meter, what I thought was 16v at the coil of the sequencer must have actually been 16mv, so basically zero. Have good voltage at thermostat, and on activation it's sending voltage to correct contacts, but no voltage at sequencer or compressor contactor. On "...
- Thu Nov 10, 2011 11:23 am
- Forum: Nordyne Service & Repair
- Topic: E2EB-012 Low Voltage
- Replies: 3
- Views: 4119
E2EB-012 Low Voltage
The other morning, when I got up I bumped the thermostat on the heat pump up a couple of degrees like I do every morning. When I did, the lamp that was on in the living room seemed to dim a little for a second, but I didn't think anything of it. After about an hour, I noticed that the fan was still ...